Paramter No. |
1 |
Size |
1 |
Default |
0 |
Name |
local protection |
Description |
enables/disables local entry. If activated module stops
responding to S1 and S2 push buttons, SCENE ID and association commands will not be sent. Only exception is the
B-button. |
Type |
rangemapped |
Values |
0 |
  ->   |
0 - no protection. Roller Shutter responds to push buttons. |
1 |
  ->   |
1 - not supported. |
2 |
  ->   |
2 - Local protection active. Roller Shutter does not respond to push buttons. |
|
  |
Paramter No. |
2 |
Size |
1 |
Default |
0 |
Name |
radio protection |
Description |
enables/disables RF protection. If activated device stops responding to command frames. Configuration and polling still possible. |
Type |
rangemapped |
Values |
0 |
  ->   |
0 – No protection. Roller Shutter responds to command frames. |
1 |
  ->   |
1 - RF Protection active. Roller Shutter does not respond to the
Z-Wave control frames. |
2 |
  ->   |
2 - not supported. |
|
  |
Paramter No. |
3 |
Size |
1 |
Default |
0 |
Name |
reports type |
Description |
Parameters value shoud be set to 1 if the module operates in
Venetian Blind mode. |
Type |
rangemapped |
Values |
0 |
  ->   |
0 – Blind position reports sent to the main controller using Z-Wave
Command Class. |
1 |
  ->   |
1 - Blind position reports sent to the main controller using Fibar
Command Class. |
|
  |
Paramter No. |
10 |
Size |
1 |
Default |
1 |
Name |
Roller Shutter operating modes |
Description |
parameter sets the operating mode. |
Type |
rangemapped |
Values |
0 |
  ->   |
0 - Roller Blind Mode, without positioning |
1 |
  ->   |
1 - Roller Blind Mode, with positioning |
2 |
  ->   |
2 - Venetian Blind Mode, with positioning |
3 |
  ->   |
3 - Gate Mode, without positioning |
4 |
  ->   |
4 - Gate Mode, with positioning |
|
  |
Paramter No. |
12 |
Size |
2 |
Default |
150 |
Name |
turning time/ delay time |
Description |
In Venetian Blind mode (parameter 10 set to 2) the
parameter determines time of full turn of the lamellas.
In Gate Mode (parameter 10 set to 3 or 4) the parameter defines the delay time after which an open gate starts closing. |
Type |
range |
Values |
-32767 0,01s - 32767 0,01s |
  ->   |
Value 0 means the gate will not close automatically. |
|
  |
Paramter No. |
13 |
Size |
1 |
Default |
1 |
Name |
lamellas positioning mode |
Description |
parameter influences the lamellas positioning in venetian blind mode (parameter 10 set to 2) |
Type |
rangemapped |
Values |
0 |
  ->   |
0 - Lamellas return to previously set position only in case of the
main controller operation. |
1 |
  ->   |
1 - Lamellas return to previously set position in case of the main controller operation, momentary switch operation, or when the
limit switch is reached. |
2 |
  ->   |
2 - Lamellas return to previously set position in case of the main
controller operation, momentary switch operation, when the limit
switch is reached or after receiving a “STOP” control frame
(Switch Multilevel Stop). |
|
  |
Paramter No. |
14 |
Size |
1 |
Default |
0 |
Name |
switch type |
Description |
parameter settings are relevant for Roller Blind Mode and
Venetian Blind Mode (parameter 10 set to 0, 1, 2). |
Type |
rangemapped |
Values |
0 |
  ->   |
0 - Momentary switches |
1 |
  ->   |
1 - Toggle switches |
2 |
  ->   |
2 - Single, momentary switch. (The switch should be connected to S1 terminal) |
|
  |
Paramter No. |
17 |
Size |
1 |
Default |
10 |
Name |
delay time after S2 |
Description |
In roller blind mode or venetian blind mode (parameter 10
set to 0, 1, 2) the parameter determines when the Roller
Shutter relays are turned off after reaching a limit switch.
In Gate Mode (parameter 10 set to 3 or 4) the parameter
determines a time period after which a gate will start closing after a S2 contact has been disconnected. |
Type |
range |
Values |
-127 0,1s - 127 0,1s |
  ->   |
value 10 = 1s.
In Gate Mode, time to turn off the Roller Shutter relays after reaching a limit switch is set to 3 seconds and cannot be modified. Value of 0 means the gate will note close automatically. |
|
  |
Paramter No. |
18 |
Size |
1 |
Default |
10 |
Name |
motor operation detection |
Description |
Power threshold to be interpreted as reaching a limit switch. |
Type |
range |
Values |
-127 1W - 127 1W |
  ->   |
The value of 0 means reaching a limit switch will not be detected. |
|
  |
Paramter No. |
22 |
Size |
2 |
Default |
240 |
Name |
motor operation time |
Description |
Time period for the motor to continue operation. |
Type |
range |
Values |
-32767 1s - 32767 1s |
  ->   |
value of 0 means the function is disabled. |
|
  |
Paramter No. |
29 |
Size |
1 |
Default |
0 |
Name |
Forced Roller Shutter calibration |
Description |
seting the parameter to 1 Roller Shutter enters the calibration mode. Parameteronly is only relevant if a Roller Shutter is set to work in positioning mode (parameter 10 set to 1, 2 or 4). |
Type |
rangemapped |
Values |
0 |
  ->   |
0 - deactivated (value 0 is automatically set after calibration process) |
1 |
  ->   |
1 - Start calibration process |
|
  |
Paramter No. |
30 |
Size |
1 |
Default |
2 |
Name |
Response to general alarm |
Description |
|
Type |
rangemapped |
Values |
0 |
  ->   |
0 - No reaction. |
1 |
  ->   |
1 - Open blind. |
2 |
  ->   |
2 - Close blind. |
|
  |
Paramter No. |
31 |
Size |
1 |
Default |
0 |
Name |
Response to flooding alarm |
Description |
|
Type |
rangemapped |
Values |
0 |
  ->   |
0 - No reaction. |
1 |
  ->   |
1 - Open blind. |
2 |
  ->   |
2 - Close blind. |
|
  |
Paramter No. |
32 |
Size |
1 |
Default |
1 |
Name |
Response to smoke, CO or CO2 alarm |
Description |
|
Type |
rangemapped |
Values |
0 |
  ->   |
0 - No reaction. |
1 |
  ->   |
1 - Open blind. |
2 |
  ->   |
2 - Close blind. |
|
  |
Paramter No. |
33 |
Size |
1 |
Default |
1 |
Name |
Response to temperature alarm |
Description |
|
Type |
rangemapped |
Values |
0 |
  ->   |
0 - No reaction. |
1 |
  ->   |
1 - Open blind. |
2 |
  ->   |
2 - Close blind. |
|
  |
Paramter No. |
35 |
Size |
1 |
Default |
1 |
Name |
Managing lamellas in response to alarm |
Description |
In Venetian Blind Mode (parameter 10 set to 2), the parameter determines how the lamellas will react upon alarm detection. |
Type |
rangemapped |
Values |
0 |
  ->   |
0 - Do not change lamellas position - lamellas return to the last set position. |
1 |
  ->   |
1 - Set lamellas to their extreme position. |
|
  |
Paramter No. |
40 |
Size |
1 |
Default |
10 |
Name |
Power reports |
Description |
Power level change that will result in new power value report being
sent. value is a percentage of the previous report. |
Type |
range |
Values |
1 1% - 100 1% |
  ->   |
Value of 0 means the reports are turned off. |
|
  |
Paramter No. |
42 |
Size |
2 |
Default |
3600 |
Name |
Periodic power or energy reports |
Description |
time to the next report |
Type |
range |
Values |
-32767 1s - 32767 1s |
  ->   |
Value of 0 means the reports are turned off. |
|
  |
Paramter No. |
43 |
Size |
1 |
Default |
10 |
Name |
Energy reports |
Description |
Energy level change which will result in new energy value report
being sent. |
Type |
range |
Values |
-126 0,01KWh - 127 0,01KWh |
  ->   |
Value of 0 means the reports are turned off. |
|
  |
Paramter No. |
44 |
Size |
1 |
Default |
0 |
Name |
Self-measurement |
Description |
enables/disables to include the power and energy used by itself in reports to main controller. |
Type |
rangemapped |
Values |
0 |
  ->   |
0 - Self-measurement inactive. |
1 |
  ->   |
1 - Self-measurement active. |
|
  |
Paramter No. |
50 |
Size |
1 |
Default |
0 |
Name |
Scenes/ Associations activation |
Description |
Parameter determines whether scenes or associations are
activated by the switch keys. |
Type |
rangemapped |
Values |
0 |
  ->   |
0 - Associations activation |
1 |
  ->   |
1 - Scenes activation |
|
  |